ROCS-PSU Power Supply, Battery Charger, UPS
|
||||
General Information It
supplies 28VDC, with up to 50A to
equipments and charge its Battery concurrently. Input Voltage - 200/208VAC 3 phase or 115/220VAC 1 phase Out Voltage - 28VDCFrequency - 45-440Hz.Output Power - 1232 watt @ +40°C
DimensionsWidth............................ 180 mm Height........................... 271 mm Depth............................ 377 mm WeightWeight is 14.5 K |
||||
Permissible Line DistortionsAccording to MIL-STD-461C CE-01, CE-03. Efficiency85% nominal
Output Current40 amps; regulated over a range of 10% to max amperes. < 1% RMS max output at 28VDC, 40 amps. Operational Temperature28VDC, 44A, 1232 watt at +30°C 28VDC, 40A, 1120 watt at +40°C 28VDC, 36.5A, 1008 watt at +50°C 28VDC, 32A, 896 watt at +60°C 28VDC, 28A, 784 watt at +70°C
CoolingNatural convection.
InsulationInput-to-chassis and input-to- output insulation exceed 20MW at 500V; output -to-chassis shall exceed 20MW at 100V. The UPS withstands dielectric voltage of 1500VDC for 1 minute between input-to-chassis and input-to-output.
Battery Protections Low Voltage Disconnect (LVD)
A furnished redundant low voltage disconnect circuit provides protection for the battery, if battery voltage decreases below a present level. The LVD circuit disconnects the battery bus at 1.8V/cell from loads, rectifier module, and protects the battery from excessive discharge. The UPS outputs dry contact close on fail to indicate that LVD is disconnected.
Emission and Susceptibility RequirementsThe RCS-PSU shall meet all the EMI/EMC requirements of MIL-STD-461C, PART 1&2, which is specified herein: CE01: Conducted Emissions, Power and Interconnecting Leads (120 Hz - 20KHz). CEO3 Conducted Emissions, Power and Interconnecting Leads (15 KHz-50KHz. CS02: Conducted Susceptibility, Power and interconnecting Leads (30 KHz to 400Mhz). CS06: Conducted Emission, Power Leads, and Spikes. RE02: Radiated Emissions, Electric Field (14 KHz to 1 GHz). RS02: Radiated Susceptibility, Magnetic Field, Electric Field, Spikes & Power Frequencies (30 Hz - 50KHz.) RS03: Radiated Susceptibility, Electric Field
|
Protections to the power supply Input protection against transients and spikes according to MIL-STD-704D Input line protected by circuit breaker. Output to battery 28VDC protected by circuit breaker. Output 28VDC to load is protected by circuit breaker. Output 28VDC to Battery is protected by circuit breaker. The power supply shuts off without damage when input voltage is above/below the specified limits. Over voltage protection Over load - over current between 105% - 115% Short circuit - the power supply withstands without damage short-circuit conditions. After removing the short circuit condition the power supply will return to normal operation by itself. Thermal ProtectionInternal thermal protection shuts off the power supply output in case of overheating. The unit automatically resumes operation after cooling down. Leakage currentLeakage current from the battery to the power supply when the power supply is in off, shall be less than 10mA.
Operating Regimes:Constant voltage, constant current with automatic crossover
The RCS-PSU is not shall not suffer damage or subsequent failure to meet the specified performance when subjected to shock environment during transportation, handling, servicing and operation. The RCS-PSU designed and built to meet the mechanical shock test requirements as specified. Test Methods MIL-STD-810D Method 516.3 Procedure I. Conditions - 40g @ 11msec/saw tooth, 3 shocks on each of 6 directions.
The RCS-PSU is designed and built to meet the humidity test requirements. The RCS-PSU shall maintain their specified performance when exposed to a relative humidity of 95% non-condensing for both continuous and intermittent periods, per MIL-STD-810C Method 507.1 (conducted for 3 cycles).
|
|||
The RCS-PS operates in low and high temperature operating conditions without experiencing physical damage or deterioration in performance test conditions of -40°C to +71°C, per MIL-STD-810D, Method 502.2 - Low Temperature, Procedure II, (-40°C for 24 hours). MIL-STD-810D, Method 501.2 - High Temperature, Procedure II, (+71°C for 24 hours). |
The RCS-PS meets the specified performance when subjected to random vibration expected during operation for ground mobile and aircraft environments per MIL-STD-810D. .
|
|||
|
||||